Part Number: ETI0005-1030
3000 VA Rugged NEMA 12 UPS
PowerStation™ Isolated UPS
3000 VA Rugged NEMA 12, Modular Power System
ETI0005-1030 Standard Front Panel and Side Panel Layout
The field proven PowerStation UPS line is ideally suited for military, industrial and telecommunications applications requiring rugged rack or table mount and/or portable construction, high reliability, compact size and light weight design. The heavy duty chassis occupies minimal space while delivering up to 3000 VA of clean, uninterruptible power. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration. An internal transformer bay accommodates the input isolation transformer with provisions for both domestic and optional international voltages for ratings up to 3000 VA. The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high intensity audible alarm can be heard in high noise environments, yet is easily adjustable to suit quieter conditions. Various optional power distribution controls are available which mount internally or remotely.
Locking connectors for the input and output power are available as options. Multiple input and output power panel options are also available. A washable intake air filter and high capacity ball bearing fan provide added protection in both controlled and hostile environments. The exhaust air is diverted out side vents. An external battery connector allows the safe and easy addition of extra battery modules without having to shut the unit down. A frequency selection switch is available for those sites requiring 50 hertz output instead of the standard 60 hertz. The status D shell connector provides signals to interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
Overall, the PowerStation line is uniquely qualified for critical industrial, shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
AC OUTPUT | |
Output voltage: | 120 VAC true sinewave std, up to 600 VAC optional |
Output rating: UPS | 3000 VA 0.65-0.75 pf std, optional configurations to 18,000 VA |
Non-linear load capacity: | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 or 50 Hz ± 2.5% synchronized to utility 60 or 50 Hz ± 1.0% w/ utility not available |
Operational status | Status, load and battery level LEDs, w/contacts Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT | |
Input voltage selection: | 120 VAC, optional up to 600 VAC, up to 440 Hz |
Input voltage tolerance: UPS | +15% -25% of nominal input rating |
Input/output isolation: | Up to 120 dB electrical noise attenuation |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole switch w/ fuse, optional breaker Guarded cold start to turn on w/o AC present |
Input power connection: | AMP CPC Type XII locking, various options |
BATTERY | |
Type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
Battery life: | Rated for continuous service life of 5 years |
DC protection: | Front panel mounted fuse, optional breaker |
Battery expansion: | Up to 24 hours w/ Battery Expansion Modules |
DISTRIBUTION PANEL | |
Output circuits: | One output standard, up to eight optional |
Output control: | Optional panel switches or breakers Optional remote interlock ON/OFF control |
Output receptacles: | MS locking std, various options |
MECHANICAL | |
Dimensions ( H x D x W ): | 36 x 16 x 30 in (914 x 406 x 762 mm) |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Shipping weight: | 215 lb. (98 kg) with lift handles front and rear |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, positive pressure, forced air |
Cooling air direction: | Side intake, exhaust to opposite side |
Air intake filter: | Washable filter media, various porosities |
ENVIRONMENTAL | |
Storage temperature: | -13° to 131° F ambient (-25° to 55° C ) |
Operating temperature: | 32° to 113° F ambient (0° to 45° C ),higher optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Operating elevation: | Up to 10,000 ft (3,048 m), higher optionally |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 810, 454 & 1399 Shock/Vib/Electrical |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC, Class A, optional MIL STD 461 |
OPTIONAL ACCESSORIES | |
Dual Source Input, Batteryless Operation, Battery Expansion Unit, Automatic Battery Test, Power Distribution Units, Software Interface |